Tie spacing · AS 3600:2018 (Amd 1 and 2)
PierKALC uses the tightest applicable limit. For limited-ductile wall boundaries in buildings over four storeys, Clause 14.6.2.3 caps spacing at the lesser of the wall thickness and 200 mm, with Clause 10.7.4 also applying.
Single-leg cross-ties. Clause 10.7.4.2 permits qualifying internal cross-ties for lateral restraint, including in taller buildings. Check the hook and restraint conditions and any closed-fitment requirements for the wall. The four-storey cutoff in Clause 14.6.2.2 applies to its deemed edge detail. PierKALC schedules closed hoops.
For enhanced confinement under Clause 14.5.4, one limit is 8 times the smallest enclosed vertical bar diameter. N12 vertical bars give a 96 mm limit and 95 mm centres on the 5 mm grid if it governs.
Ways to increase spacing
- If 8 times the vertical bar diameter governs, try a larger minimum vertical bar size. N16 raises this limit to 128 mm. Check the new governing limit and bar layout.
- If concrete above 50 MPa triggers whole-wall confinement under Clause 14.6.3, consider 50 MPa or lower where strength, durability and the project specification permit. Other restraint requirements can still govern.
- If tie diameter or core confinement pressure governs, try a larger tie and check cover and fit. If wall thickness governs, a thicker wall may help.
Rerun the design after any change. The report shows the governing limit.