Shear Wall Designer · AS 3600:2018 with Amendments 1 and 2

Wall section

Design settings

Tie spacing · AS 3600:2018 (Amd 1 and 2)

PierKALC uses the tightest applicable limit. For limited-ductile wall boundaries in buildings over four storeys, Clause 14.6.2.3 caps spacing at the lesser of the wall thickness and 200 mm, with Clause 10.7.4 also applying.

Single-leg cross-ties. Clause 10.7.4.2 permits qualifying internal cross-ties for lateral restraint, including in taller buildings. Check the hook and restraint conditions and any closed-fitment requirements for the wall. The four-storey cutoff in Clause 14.6.2.2 applies to its deemed edge detail. PierKALC schedules closed hoops.

For enhanced confinement under Clause 14.5.4, one limit is 8 times the smallest enclosed vertical bar diameter. N12 vertical bars give a 96 mm limit and 95 mm centres on the 5 mm grid if it governs.

Ways to increase spacing

  • If 8 times the vertical bar diameter governs, try a larger minimum vertical bar size. N16 raises this limit to 128 mm. Check the new governing limit and bar layout.
  • If concrete above 50 MPa triggers whole-wall confinement under Clause 14.6.3, consider 50 MPa or lower where strength, durability and the project specification permit. Other restraint requirements can still govern.
  • If tie diameter or core confinement pressure governs, try a larger tie and check cover and fit. If wall thickness governs, a thicker wall may help.

Rerun the design after any change. The report shows the governing limit.

Ultimate Design Actions

Enter negative N for compression. M22 bends out of plane and M33 bends in plane. V22 is the in-plane shear; V33 is recorded for reference.

CombinationEndN (kN)M22 (kN·m)M33 (kN·m)V22 (kN)V33 (kN)Remove